omron.v7
Частотный преобразователь Omron V7.
Используемый протокол - MODBUS.
http://www.omronkft.hu/nostree/pdfs/inverter/cimr-v7az/v7az.pdf
plugin.peripherial: module.icp1: portnum: 2 netaddr: 1 enable: on type: omron.v7
Теги
Reg0001 Reg0002 Reg0020 Reg0021 Reg0022 Reg0023 Reg0024 Reg0027 Reg0028 Reg0029 Reg002A SYSTEM.ErrorCount SYSTEM.ErrorFlag SYSTEM.NetAddr SYSTEM.Port SYSTEM.TimePeriod SYSTEM.UpdateDate SYSTEM.UpdateTime
Регистры
- Reg0001
- 0 Run Command - 1: Run, 0: Stop
- 1 Reverse Run Command 1: Reverse run 0: Forward run
- 2 External fault 1: Fault (EFO)
- 3 Fault Reset Command 1: Reset Command
- 4 Multi-function input reference 1 (Function selected by n050)
- 5 Multi-function input reference 2 (Function selected by n051)
- 6 Multi-function input reference 3 (Function selected by n052)
- 7 Multi-function input reference 4 (Function selected by n053)
- 8 Multi-function input reference 5 (Function selected by n054)
- 9 Multi-function input reference 6 (Function selected by n055)
- A Multi-function input reference 7 (Function selected by n056)
- B-F (Not used)
- Reg0002 - Frequency reference (unit: n152)
- Reg0020 - Status signal
- 0 Run Command 1: Run 0: Stop
- 1 Reverse Run Command 1: Reverse run 0: Forward run
- 2 Inverter operation ready 1: Ready 0: Not ready
- 3 Fault 1: Fault
- 4 Data setting error 1: Error
- 5 Multi-function output 1 (1: MA ON 0: MA OFF)
- 6 Multi-function output 2 (1: P1 ON 0: P1 OFF)
- 7 Multi-function output 3 (1: P2 ON 0: P2 OFF)
- 8-F (Not used)
- Reg0021 - Fault description
- 0 Overcurrent (OC)
- 1 Overvoltage (OV)
- 2 Inverter overload (OL2)
- 3 Inverter overheat (OH)
- 4 (Not used)
- 5 (Not used)
- 6 PID feedback loss (FbL)
- 7 External fault (EF, EFO), Emergency stop (STP)
- 8 Hardware fault (FXX)
- 9 Motor overload (OL1)
- A Overtorque detection (OL3)
- B Undertorque detection (UL3)
- C Power loss (UV1)
- D Control power fault (UV2)
- E MEMOBUS communications timeover (CE)
- F Operator connection fault (OPR
- Reg0022 - Data link status
- 0 Data write in
- 1 (Not used)
- 2 (Not used)
- 3 Upper/lower limit fault
- 4 Consistency fault
- 5-F (Not used)
- Reg0023 - Frequency reference (unit: n152)
- Reg0024 - Output frequency (unit: n152)
- Reg0027 - Output current (10/1 A)
- Reg0028 - Output voltage reference (1/1 V)
- Reg0029 - Fault description
- 0 (Not used)
- 1 (Not used)
- 2 Input open phase (PF)
- 3 Output open phase (LF)
- 4-F (Not used)
- Reg002A - Alarm description
- 0 Operation function stop (STP)
- 1 Sequence error (SER)
- 2 Simultaneous FWD/REV Run Commands (EF)
- 3 External Baseblock (BB)
- 4 Overtorque detection (OL3)
- 5 Cooling fan overheat (OH)
- 6 Main circuit overvoltage (OV)
- 7 Main circuit undervoltage (UV)
- 8 Cooling fan fault (FAN)
- 9 Communications fault (CE)
- A Option card communications error (BUS)
- B Undertorque (UL3)
- C Inverter overheat alert (OH3)
- D PID feedback loss (FBL)
- E Emergency stop (STP)
- F Communications waiting (CAL)